Specifications / Information Provided in Report

Capacity Evaluation Report, Battery Performance Badge Available Day Of Test

Battery Performance Badge Attaches To Battery String For Future Reference

Battery - EKG Battery Performance Information Provided in Report

Battery Test Results In Report

Typical Accuracy (at test time)

 Overall String Voltage  ± 0.003 volts
 Individual Cell Voltages  ± 0.0002 volts
 Intercell Connection Resistance*  ± 20 microohms and ± 15 %
 Individual Cell Capacities*  ± 10 %
 Overall String Capacity (or Reserve Time)*  ± 7 % (± 12 %)
 Results From Previous Test*  

* Provided on Battery Performance Badge

Options
 Electrolyte Specific Gravity Measurement
 Negative Plate Polarization Analysis
 Battery Temperature Capacity Correction
 Specified E.O.D. Voltage Capacity Correction
 Specified Discharge Rate Capacity Correction
 Capacity Expressed as Reserve Time (based on load, and parallel strings)
 Battery Rectifier Current Harmonic Content Evaluation